Data Center Rack and Power Installation
Rack, power and patching work in your own data center or a cage you lease: equipment racked to an elevation, power planned per circuit, and every port labelled.
On site in Southern California. Hardware we supply ships anywhere.
What You Get
Included
- Rack elevations drawn before the visit
- Power planned per circuit: the draw of each device on its A and B feeds
- Equipment racked, powered and patched to the plan
- Ports labelled to match the label map you keep
- An as-built handed over at the end of the visit
Not included
- Rack space or servers of ours to rent
- Electrical or mechanical work that needs a licensed contractor
- Remote hands on call
- 24/7 monitoring, alerting or on-call
Structured cabling installation is performed by licensed C-7 partners under our project management.
The Power Plan
Drawn before the visit, so nothing trips a breaker on the day. Each device draws from two feeds, A and B, so either can carry the rack alone. The excerpt below is a sample, with fictional devices.
| Rack · U | Device | Feed A | Feed B | Draw |
|---|---|---|---|---|
| R1 · 42 | SW-CORE-01 | PDU-A 12 | PDU-B 12 | 180 W |
| R1 · 40 | FW-01 | PDU-A 11 | PDU-B 11 | 90 W |
| R1 · 30–31 | SRV-01 | PDU-A 6 | PDU-B 6 | 650 W |
| R1 · 28–29 | SRV-02 | PDU-A 5 | PDU-B 5 | 650 W |
| R1 | Total, carried by one feed if the other fails | 1,570 W | ||
| R1 | Each feed: 20 A at 208 V, 3,328 W usable at 80% | 47% load |